FireCom2

Fireman Intercom System -up to 1016 Remote Handset (RHS) connection

System

  • Model : FireCom2
  • Type I : Conventional Type (CT) (All RHS wire connection at Main Intercom Panel)
  • Type 2 : Distributed Transponder Type (DTT) (RHS wire connection at DTU)
  • Standard Compliance : Singapore Standard SS546 : 2022
  • Color : Signal Red (RAL 3001)
  • Operating Voltage : 27.5Vdc
  • Incoming Main Supply : 120Vac-240Vac (50/60Hz)
  • Standby Power Source : Sealed Lead Acid Maintenance Free Batteries
  • Intercom System : Two-way Emergency Voice Communication System
  • Maximum Handsets Connection : Up to 1016 Remote Hndsets (RHS)

Master Handset (MHS)

  • Model : PI-HS2 (MHS)
  • Handset Color : Tomato Red (RAL 3013)
  • Operating Voltage : 15Vdc
  • Quiescent Current : 2mA
  • Talk Time Current : 12mA
  • Ring Tone : 300Hz (Speaker) & Buzzer
  • Microphone : Electret type
  • Speaker : 16 Ohm
  • Audio Frequency Response : 150 - 4.2kHz

System Control Module (SCM)

A. Indications

  • Model : PI-SCM-2
  • Charger Fault : Mains failure, Charger low, Fuse blown
  • Battery Fault : Battery disconnected, Battery low, Fuse blown
  • Loop Fault : 24V Supply, Audio, Data communications line fault
  • Master Handset Fault : MHS disconnected
  • Earth Fault : Wire shorted to earth
  • Fire : Fire activated signal received
  • Recording On : Recording in progress
  • Handsets Connected : MHS and RHS are connected
  • Recorder Fault : Memory card not in place (Optional item)
  • Private/All Parties Indication : System status in private or All Parties mode

B. Switches

  • Private/All Parties Selector : Switch between Private & All Parties mode
  • Buzzer Silence : Silence buzzer
  • Lamp test Switch : Check considtions of LED indications & buzzer
  • Reset Switch : Reset system

Zone Control Module (ZCM)

  • Model : PI-ZCM-2
  • Call Indications : Blinking - RHS calling, Steady - RHS and MHS connected
  • Fault Indication : RHS Line shorted / Open circuit fault
  • Call/Accept Switch : Call individual RHS or Accept call from RHS
  • Nos of Zone (RHS) per card : 8 Zone (RHS)
  • Operating Voltage : 12Vdc
  • Quiscent Current : 20mA